Features
- Supply 85-264Vac 50/60Hz, 20-28Vac/dc 50/60Hz
- 18 types of input: thermocouple (10 types), RTD (2 types), DC current (2 types) and DC voltage (4 types)
- Two types of setting value can be switched externally
- 3 types of output: Relay contact 3A 250Vac (resistive load), 1A 250Vac (inductive load) Non-contact DC voltage: 12-14Vdc Max. 40mA (short circuit protected) DC current: 4 to 20mA load resistance Max 550 ohms
- Alarm output: Relay contact 3A 250Vac (resistive load)
- Wide range of communication functions
- Water and dust proof (IP66)
- UL/CSA and CE marking
- Shipped ready to use
- Dimensions: W48 x H48 x D96.5mm
Ranges
- Scale ranges from -200°C to 2315°C
Options
- Alarm 2 output: Relay contact 3A 250Vac (resistive load)
- Heater break Alarm: Current transformer detects burnout Heater rated current 5A, 10A, 20A and 50A Setting accuracy- within +/-5% of heater rated current Output: Relay contact 3A 250Vac (resistive load)
- Control output 2 to enable Heating/Cooling control
- Serial Comms: Based on EIA, RS-485 Protocol: Based on Shinko standard protocol or Modbus (Selectable by key operation) Number of connecable units: A maximum of 31 units per host computer